Carbon Dioxide Emission from People
Carbon Dioxide emission from persons depends on activity
The Carbon Dioxide - CO2 - concentration in a room with people can be used to indicate ventilation system efficiency. It is even possible to modulate ventilation system capacities to the number of people and their activities by measuring the carbon dioxide concentration in the room air.
Carbon dioxide emission from persons and their activity:
Activity | Respiration per Person (m3/h) | Carbon Dioxide Emission per Person (m3/h) |
---|---|---|
Sleep | 0.3 | 0.013 |
Resting or low activity work | 0.5 | 0.02 |
Normal work | 2 - 3 | 0.08 - 0.13 |
Hard work | 7 - 8 | 0.33 - 0.38 |
- 1 m3/h = 0.5886 ft3/min (cfm)
Example - Carbon Dioxide Emission from Persons in a Cinema
In a cinema with 100 persons with low to normal activity the emission of carbon dioxide is in the range 0.02 to 0.08 m3/h per person and the the total emission will be in the range 2 to 8 m3/h.