Fuel Gases - Combustion Values
Combustion (heat) values for some fuel gases:
| Fuel Gas | Combustion Value (Btu/ft3) | Specific Gravity |
|---|---|---|
| Acetylene | 1498 | 0.91 |
| Blast furnace gas | 92 | 1.02 |
| Butane | 3184 | 1.95 (heavier than air) |
| Butylene (Butene) | 3077 | 1.94 |
| Carbon Monoxide | 323 | 0.97 |
| Carburated Water Gas | 550 | 0.63 |
| Coke oven | 570 | 0.40 |
| Digester (Sewage) Gas | 690 | 0.80 |
| Ethane | 1783 | 1.06 |
| Hydrogen | 325 | 0.07 |
| Manufactured Gas | 500 - 600 | |
| Methane | 1011 | 0.55 |
| Natural Gas | 950 - 1150 | 0.660 - 0.708 (lighter than air) |
| Propane | 2504 | 1.77 |
| Propane-Butane Mix | 2500 - 3200 | |
| Propylene (Propene) | 2332 | 1.45 |
| Water Gas (bituminous) | 261 | 0.71 |
- 1 Btu/ft3 = 8.9 kcal/m3 = 3.73×104 J/m3
Related Topics
• Combustion
Combustion processes and their efficiency. Boiler house and chimney topics. Properties of fuels like oil, gas, coal and wood and more. Safety valves and tanks.
Related Documents
Butane - Dynamic and Kinematic Viscosity vs. Temperature and Pressure
Online calculators, figures and tables with dynamic and kinematic viscosity of liquid and gaseous butane, C4H10, at varying temperarure and pressure, SI and Imperial units.
Fuel Gases - Wobbe Index
Wobbe index for fuel gases like propane, butane, methane and more.
Fuels - Combustion Air and Flue Gases
Combustion air and flue gas for common fuels - coke, oil, wood, natural gas and more.
Gases - Gross and Net Heat Values
Gross heat and net heat values for gases like hydrogen, methane and more.
Heating Fuels - Cost Comparing
Cost comparison formulas for heating fuels like Natural Gas, Propane LP Gas, Fuel Oil and Electricity.
Paraffins and Alkanes - Combustion Properties
Properties like heat values, air/fuel ratios, flame speed, flame temperatures, ignition temperatures, flash points and flammability limits.