Copper Tube Supports
Maximum space between supports aand clips for copper tubes
Copper Tubes - Maximum space between Supports | |||||
---|---|---|---|---|---|
Size | Horizontal Run | Vertical Run | |||
(mm) | (in) | (m) | (ft) | (m) | (ft) |
6 | 0.4 | 1.3 | 0.6 | 2 | |
8 | 0.6 | 2 | 0.9 | 3 | |
10 | 3/8 | 0.8 | 2.6 | 1.2 | 4 |
12 | 1.0 | 3.3 | 1.5 | 5 | |
15 | 1/2 | 1.2 | 4 | 1.8 | 6 |
22 | 3/4 | 1.2 | 4 | 1.8 | 6 |
28 | 1 | 1.5 | 5 | 2.4 | 8 |
35 | 1 1/4 | 1.8 | 6 | 3.0 | 10 |
42 | 1 1/2 | 1.8 | 6 | 3.0 | 10 |
54 | 2 | 1.8 | 6 | 3.0 | 10 |
67 | 2 1/2 | 2.4 | 8 | 3.7 | 12 |
76 | 3 | 2.4 | 8 | 3.7 | 12 |
108 | 4 | 2.4 | 8 | 3.7 | 12 |
133 | 5 | 3.0 | 10 | 3.7 | 12 |
159 | 6 | 3.7 | 12 | 3.7 | 12 |
Example - Support of Copper Tube
The maximum distance between the horizontal supports of a 1" (28 mm) copper tube is 5 ft (1.5 m).