Pressfit Pipes - Supports
NPS
(inches)
DN
(mm)
Support Spacing (feet)
Water ServiceGas or Air Service
B31.1B31.3B31.9B31.1B31.3B31.9
1/2 15 6 6 7 8 8 7
3/4 20 7 7 8 9 9 8
1 25 7 7 9 9 9 9
1 1/4 32 7 7 11 9 9 11
1 1/2 40 7 7 12 9 9 13
2 50 10 10 13 13 13 15