Outdoor Temperatures and Relative Humidity - U.S. Winter and Summer Conditions
The table below indicates the summer and winter design conditions in U.S. states and cities.
For full table with Summer Condtions - rotate the screen!
| State | City | January | July | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Daily Temperature (oF) | Design Dry Bulb Temperature (oF) | Normal Relative Humidity (%) | Average Daily Temperature (oF) | Design Dry Bulb Temperature (oF) | Normal Relative Humidity (%) | ||||||
| 7:30 am. | 1:30 pm. | 7:30 pm. | 7:30 am. | 1:30 pm. | 7:30 pm. | ||||||
| Alabama | Birmingham | 10 | 81 | 61 | 66 | 95 | 84 | 56 | 68 | ||
| Mobile | 52.5 | 10 | 81.5 | 95 | 90 | 64 | 78 | ||||
| Arizona | Flagstaff | -10 | 83 | 58 | 90 | 77 | 36 | ||||
| Phoenix | 53.9 | 25 | 75 | 47 | 39 | 89.6 | 105 | 53 | 31 | 23 | |
| Yuma | 30 | 56 | 37 | 27 | 110 | 51 | 31 | 23 | |||
| Arkansas | Little Rock | 42.4 | 5 | 80 | 67 | 68 | 80.5 | 95 | 85 | 55 | 59 |
| California | Eureka | 30 | 87 | 77 | 90 | 92 | 80 | ||||
| Fresno | 25 | 93 | 80 | 66 | 105 | 61 | 36 | 20 | |||
| Los Angeles | 52.1 | 35 | 63 | 46 | 51 | 68.3 | 90 | 85 | 50 | 54 | |
| Sacramento | 30 | 90 | 82 | 70 | 100 | 76 | 46 | 28 | |||
| San Diego | 35 | 76 | 58 | 60 | 85 | 86 | 68 | 65 | |||
| San Francisco | 35 | 84 | 69 | 70 | 85 | 92 | 75 | 78 | |||
| Colorado | Denver | 31.9 | -10 | 54 | 37 | 41 | 70.6 | 95 | 55 | 27 | 30 |
| Grand Junction | -15 | 77 | 64 | 64 | 95 | 48 | 27 | 22 | |||
| Pueblo | -20 | 67 | 44 | 48 | 95 | 73 | 34 | 35 | |||
| Connecticut | New Haven | 0 | 75 | 65 | 69 | 95 | 77 | 64 | 74 | ||
| Delaware | Wilmington | 33.3 | 0 | 77 | 62 | 70 | 74.0 | 95 | 80 | 52 | 69 |
| District of Columbia | Washington | 37.2 | 0 | 73 | 56 | 64 | 77.0 | 95 | 78 | 52 | 64 |
| Florida | Jacksonville | 25 | 89 | 56 | 75 | 95 | 85 | 57 | 76 | ||
| Miami | 67.8 | 35 | 87 | 59 | 75 | 82.0 | 91 | 83 | 64 | 76 | |
| Georgia | Atlanta | 43.8 | 10 | 80 | 64 | 69 | 77.5 | 95 | 83 | 57 | 68 |
| Augusta | 10 | 84 | 59 | 69 | 98 | 83 | 55 | 69 | |||
| Savannah | 20 | 83 | 58 | 72 | 95 | 85 | 61 | 80 | |||
| Idaho | Boise | 32.7 | -10 | 82 | 75 | 74 | 70.8 | 95 | 54 | 34 | 23 |
| Lewiston | -5 | 79 | 73 | 71 | 95 | 64 | 37 | 25 | |||
| Illinois | Cairo | 0 | 81 | 69 | 98 | 83 | 57 | ||||
| Chicago | 25.0 | -10 | 81 | 70 | 75 | 71.2 | 95 | 78 | 51 | 55 | |
| Peoria | -10 | 73 | 72 | 77 | 96 | 81 | 53 | 58 | |||
| Indiana | Fort Wayne | -10 | 84 | 75 | 81 | 95 | 84 | 53 | 58 | ||
| Indianapolis | 29.1 | -10 | 83 | 72 | 78 | 73.4 | 95 | 84 | 54 | 60 | |
| Terre Haute | 0 | 82 | 70 | 76 | 95 | 77 | 50 | 56 | |||
| Iowa | Davenport | -15 | 95 | ||||||||
| Sioux City | -20 | 78 | 67 | 72 | 95 | 86 | 55 | 54 | |||
| Kansas | Dodge City | -10 | 78 | 57 | 61 | 95 | 77 | 45 | 52 | ||
| Topeka | -10 | 78 | 64 | 67 | 100 | 85 | 54 | 54 | |||
| Kentucky | Louisville | 35.2 | 0 | 78 | 68 | 69 | 75.9 | 95 | 77 | 52 | 57 |
| Louisiana | New Orleans | 53.9 | 20 | 85 | 67 | 73 | 81.3 | 95 | 84 | 64 | 72 |
| Shreveport | 20 | 83 | 67 | 66 | 100 | 86 | 56 | 62 | |||
| Maine | Portland | 23.4 | -5 | 81 | 65 | 74 | 65.6 | 90 | 78 | 58 | 76 |
| Maryland | Baltimore | 34.6 | 0 | 72 | 68 | 56 | 74.8 | 95 | 71 | 52 | 65 |
| Massachusetts | Boston | 31.3 | 0 | 72 | 59 | 67 | 71.1 | 92 | 72 | 55 | 70 |
| Michigan | Detroit | 25.9 | -10 | 82 | 71 | 77 | 70.0 | 95 | 74 | 50 | 56 |
| Grand Rapids | -10 | 85 | 78 | 80 | 95 | 76 | 51 | 54 | |||
| Minnesota | Duluth | -25 | 78 | 74 | 74 | 93 | 87 | 61 | 66 | ||
| Minneapolis | 16.0 | -20 | 82 | 72 | 75 | 70.6 | 95 | 82 | 54 | 54 | |
| Mississippi | Vicksburg | 10 | 82 | 65 | 67 | 95 | 87 | 61 | 70 | ||
| Missouri | Kansas City | -10 | 78 | 64 | 66 | 100 | 76 | 48 | 47 | ||
| St. Louis | 32.3 | 0 | 77 | 65 | 68 | 76.9 | 95 | 73 | 50 | 55 | |
| Montana | Billings | -25 | 67 | 73 | 60 | 90 | 65 | 40 | 33 | ||
| Butte | -20 | 76 | 70 | 71 | 95 | 82 | 36 | 33 | |||
| Nebraska | North Platte | -20 | 80 | 62 | 66 | 85 | 84 | 50 | 46 | ||
| Omaha | 24.9 | -10 | 82 | 68 | 73 | 75.3 | 65 | 80 | 51 | 51 | |
| Nevada | Reno | 34.0 | -5 | 82 | 67 | 54 | 66.2 | 95 | 72 | 25 | 20 |
| New Hampshire | Concord | 22.2 | -15 | 78 | 60 | 69 | 67.1 | 90 | 80 | 49 | 69 |
| New Jersey | Atlantic City | 33.6 | 5 | 79 | 68 | 74 | 72.2 | 95 | 81 | 72 | 82 |
| Newark | 0 | 72 | 79 | 65 | 95 | 75 | 51 | 65 | |||
| Trenton | 0 | 73 | 62 | 68 | 95 | 77 | 55 | 68 | |||
| New Mexico | Albuquerque | 36.6 | 0 | 68 | 51 | 46 | 76.4 | 95 | 59 | 33 | 28 |
| New York | Albany | -10 | 75 | 63 | 71 | 93 | 79 | 52 | 64 | ||
| Buffalo | -5 | 79 | 72 | 78 | 93 | 78 | 53 | 63 | |||
| New York | 33.8 | 0 | 72 | 61 | 66 | 74.5 | 95 | 75 | 58 | 68 | |
| Rochester | -5 | 81 | 73 | 79 | 95 | 80 | 50 | 60 | |||
| North Carolina | Asheville | 0 | 82 | 59 | 69 | 93 | 88 | 56 | 73 | ||
| Raleigh | 41.1 | 10 | 82 | 57 | 69 | 76.2 | 95 | 86 | 55 | 72 | |
| North Dakota | Bismarck | 12.2 | -30 | 77 | 71 | 75 | 67.8 | 95 | 85 | 52 | 49 |
| Ohio | Cincinnati | 0 | 82 | 70 | 74 | 95 | 84 | 52 | 60 | ||
| Cleveland | 28.0 | 0 | 81 | 72 | 79 | 69.8 | 95 | 79 | 52 | 58 | |
| Columbus | -10 | 83 | 71 | 76 | 95 | 78 | 52 | 60 | |||
| Toledo | -10 | 79 | 72 | 75 | 95 | 76 | 52 | 59 | |||
| Oklahoma | Oklahoma City | 38.9 | 0 | 79 | 62 | 65 | 80.0 | 101 | 80 | 49 | 51 |
| Oregon | Baker | -5 | 83 | 81 | 78 | 90 | 69 | 68 | 36 | ||
| Portland | 41.0 | 10 | 87 | 82 | 78 | 63.8 | 90 | 86 | 63 | 48 | |
| Pennsylvania | Harrisburg | 0 | 72 | 49 | 65 | 95 | 78 | 51 | 62 | ||
| Philadelphia | 0 | 74 | 65 | 68 | 95 | 78 | 52 | 65 | |||
| Pittsburgh | 29.0 | 0 | 77 | 67 | 63 | 70.2 | 95 | 80 | 52 | 63 | |
| Scranton | -5 | 80 | 67 | 95 | 77 | 50 | |||||
| Rhode Island | Providence | 29.9 | 0 | 73 | 60 | 67 | 70.1 | 93 | 79 | 57 | 73 |
| South Carolina | Charleston | 15 | 87 | 55 | 76 | 95 | 88 | 64 | 82 | ||
| Columbia | 46.2 | 10 | 81 | 57 | 65 | 79.6 | 95 | 83 | 56 | 68 | |
| South Dakota | Huron | -20 | 79 | 72 | 76 | 95 | 86 | 52 | 49 | ||
| Rapid City | -20 | 71 | 69 | 67 | 95 | 71 | 42 | 40 | |||
| Tennessee | Knoxville | 0 | 83 | 65 | 69 | 95 | 83 | 55 | 66 | ||
| Memphis | 0 | 82 | 67 | 73 | 95 | 85 | 55 | 59 | |||
| Texas | Amarillo | -10 | 71 | 51 | 52 | 100 | 77 | 43 | 42 | ||
| Corpus Christi | 20 | 88 | 66 | 75 | 95 | 93 | 58 | 68 | |||
| Dallas | 10 | 81 | 62 | 62 | 100 | 79 | 50 | 47 | |||
| El Paso | 10 | 63 | 45 | 39 | 100 | 60 | 37 | 30 | |||
| Houston | 53.3 | 20 | 85 | 66 | 73 | 82.1 | 95 | 90 | 58 | 66 | |
| San Antonio | 20 | 82 | 60 | 59 | 100 | 88 | 49 | 45 | |||
| Utah | Salt Lake City | 31.0 | -10 | 80 | 71 | 72 | 73.5 | 95 | 56 | 27 | 23 |
| Vermont | Burlington | 19.1 | -10 | 81 | 69 | 78 | 67.3 | 90 | 76 | 54 | 67 |
| Virginia | Richmond | 38.5 | 15 | 84 | 60 | 68 | 76.0 | 95 | 81 | 57 | 72 |
| Washington | Seattle | 41.0 | 15 | 86 | 80 | 74 | 63.0 | 85 | 86 | 63 | 47 |
| Walla Walla | -5 | 80 | 74 | 78 | 95 | 50 | 33 | 22 | |||
| West Virginia | Charleston | 35.1 | 0 | 79 | 64 | 70 | 73.0 | 95 | 88 | 53 | 67 |
| Parkersburg | -10 | 82 | 66 | 74 | 95 | 80 | 52 | 65 | |||
| Wisconsin | Green Bay | -15 | 75 | 68 | 73 | 95 | 85 | 58 | 64 | ||
| Milwaukee | 22.3 | -15 | 76 | 70 | 73 | 68.2 | 95 | 81 | 58 | 64 | |
| Wyoming | Cheyenne | 28.2 | -15 | 59 | 48 | 55 | 65.9 | 95 | 73 | 36 | 40 |
Related Topics
• Air Conditioning Systems
Design of Air Conditioning systems - heating, cooling and dehumidification of indoor air for thermal comfort.
• Air Psychrometrics
Moist and humid air calculations. Psychrometric charts and Mollier diagrams. Air-condition systems temperatures, absolute and relative humidities and moisture content in air.
• Heating Systems
Design of heating systems - capacities and design of boilers, pipelines, heat exchangers, expansion systems and more.
• HVAC Systems
Design and sizing of Heating, Ventilation and Air Conditioning systems.
Related Documents
Dry Bulb, Wet Bulb and Dew Point Temperatures
Dry Bulb, Wet Bulb and Dew Point temperatures can be used to determine the state of humid air.
Fixed Temperature Points
Temperature points that can be used as a reference for calibration
Globe Temperature
The resultant or globe temperature.
Indoor Conditions - Summer or Winter
Recommended indoor design conditions summer or winter.
Indoor Relative Humidity vs. Outdoor Relative Humidity and Temperature
Recommended indoor relative humidity vs. outdoor relative humidity and temperature.
Pt100 - Platinum Resistance Thermometer
Pt100 electrical resistance temperature sensor - ranging -220 to 750 degrees Celsius.
RTD Resistance Temperature Sensor
Thermal resistive sensor - a basic introduction.
Saturated Salt Solutions - Controlling Air Humidity
A salt solutions can be used maintain a particular value of relative humidity.