Cold Water Storage per Occupant
Typical cold water storage per occupant:
| Type of building | Storage | |
|---|---|---|
| liter | gal | |
| Factories (no process) | 10 | 2 |
| Hospitals, per bed | 135 | 30 |
| Hospitals, per staff on duty | 45 | 10 |
| Hostels | 90 | 20 |
| Hotels | 135 | 30 |
| Houses and flats | 135 | 30 |
| Offices with canteens | 45 | 10 |
| Offices without canteen | 35 | 8 |
| Restaurant per meal | 7 | 1.5 |
| Schools, boarding | 90 | 20 |
| Schools, day | 30 | 7 |
Related Topics
• Water Systems
Design of hot and cold water service and utility systems with properties, capacities, sizing of pipe lines and more.
Related Documents
Cold Water Dwellings - Storage Capacities
Required cold water dwelling storage capacity - commonly used fixtures and types of buildings.
DFU - Drainage Fixture Units
DFU are used to calculate the drainage flow from fixtures and the required capacities of sewer service systems.
Domestic Hot Water Service Systems - Design Procedures
Design procedures for domestic hot water service systems.
Domestic Service Water Supply Systems
Introduction to general design of domestic service water supply systems - with pressurized or gravity tanks.
Fixture Water Consumption and Required Water Supply
Supply requirements for common fixtures.
Hot and Cold Water Pipes Sizing
Recommended dimensions hot and cold water pipes.
Water Supply Fixture Units - WSFU vs. GPM and Liters/sec
Converting WSFU - Water Supply Fixture Units - to GPM.
Water Supply Fixture Units WSFU
WSFU is used to calculate water supply service systems.
Water Supply Lines - Sizing
Sizing water supply service and distribution lines based on Water Supply Fixture Units (WSFU).
Water Supply Systems - Online Design Application
Free online tool for designing water supply systems in buildings.