PVC Pipes Schedule 40 - Friction Loss vs. Water Flow
Friction loss and flow velocities in PVC and CPVC pipes Schedule 40 with water are indicated in the table below. The table can be used for pipes in other thermoplastic materials where the inner diameter corresponds to PVC Pipe
Schedule 40.
- 1 ft (foot) = 0.3048 m
- 1 ft/s = 0.3048 m/s
- 1 gal (US)/min = 6.30888×10-5 m3/s = 0.227 m3/h = 0.0631 dm3(liter)/s = 2.228×10-3 ft3/s = 0.1337 ft3/min
- 1 psi/100 ft = 2.3 ftH2O/100 ft = 2262 mmH2O/100 m = 22.6 kPa/100 m
Note! Velocities should not exceed 5 feet per second.
The values can be used to calculate minor pressure loss with the Equivalent Pipe Length Method.
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ftH2O/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 1 | 60 | 1.1 | 2.1 | 0.9 |
| 2 | 120 | 2.3 | 4.2 | 1.8 |
| 5 | 300 | 5.6 | 23.4 | 10.5 |
| 7 | 420 | 7.9 | 43.1 | 18.6 |
| 10 | 600 | 11.3 | 82.0 | 35.5 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 1 | 60 | 0.6 | 0.5 | 0.2 |
| 2 | 120 | 1.3 | 1.0 | 0.4 |
| 5 | 300 | 3.2 | 5.7 | 2.5 |
| 7 | 420 | 4.4 | 10.5 | 4.6 |
| 10 | 600 | 6.3 | 20.0 | 8.7 |
| 15 | 900 | 9.5 | 42.5 | 18.4 |
| 20 | 1200 | 12.7 | 72.3 | 31.3 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 2 | 120 | 0.8 | 0.6 | 0.2 |
| 5 | 300 | 1.9 | 1.7 | 0.8 |
| 7 | 420 | 2.7 | 3.2 | 1.4 |
| 10 | 600 | 3.9 | 6.0 | 2.6 |
| 15 | 900 | 5.8 | 12.8 | 5.5 |
| 20 | 1200 | 7.7 | 21.8 | 9.4 |
| 25 | 1500 | 9.7 | 32.9 | 14.2 |
| 30 | 1800 | 11.6 | 46.1 | 20.0 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 2 | 120 | 0.4 | 0.1 | 0.1 |
| 5 | 300 | 1.1 | 0.4 | 0.2 |
| 7 | 420 | 1.6 | 0.8 | 0.4 |
| 10 | 600 | 2.2 | 1.6 | 0.7 |
| 15 | 900 | 3.3 | 3.3 | 1.4 |
| 20 | 1200 | 4.4 | 5.6 | 2.4 |
| 25 | 1500 | 5.5 | 8.5 | 3.7 |
| 30 | 1800 | 6.6 | 11.9 | 5.1 |
| 35 | 2100 | 7.7 | 15.8 | 6.8 |
| 40 | 2400 | 8.8 | 20.2 | 8.7 |
| 45 | 2700 | 9.9 | 25.1 | 10.9 |
| 50 | 3000 | 11.1 | 30.5 | 13.2 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 2 | 120 | 0.3 | 0.1 | 0.03 |
| 5 | 300 | 0.8 | 0.2 | 0.1 |
| 7 | 420 | 1.1 | 0.4 | 0.2 |
| 10 | 600 | 1.6 | 0.7 | 0.3 |
| 15 | 900 | 2.4 | 1.5 | 0.7 |
| 20 | 1200 | 3.2 | 2.6 | 1.1 |
| 25 | 1500 | 4.0 | 4.0 | 1.7 |
| 30 | 1800 | 4.9 | 5.5 | 2.4 |
| 35 | 2100 | 5.7 | 7.4 | 3.2 |
| 40 | 2400 | 6.5 | 9.4 | 4.1 |
| 45 | 2700 | 7.3 | 11.7 | 5.1 |
| 50 | 3000 | 8.1 | 14.3 | 6.2 |
| 60 | 3600 | 9.7 | 20.0 | 8.7 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 5 | 300 | 0.5 | 0.07 | 0.03 |
| 7 | 420 | 0.7 | 0.1 | 0.05 |
| 10 | 600 | 1.0 | 0.2 | 0.09 |
| 15 | 900 | 1.5 | 0.5 | 0.2 |
| 20 | 1200 | 2.0 | 0.8 | 0.3 |
| 25 | 1500 | 2.4 | 1.2 | 0.5 |
| 30 | 1800 | 2.9 | 1.6 | 0.7 |
| 35 | 2100 | 3.4 | 2.2 | 0.9 |
| 40 | 2400 | 3.9 | 2.8 | 1.2 |
| 45 | 2700 | 4.4 | 3.4 | 1.5 |
| 50 | 3000 | 4.9 | 4.2 | 1.8 |
| 60 | 3600 | 5.9 | 5.8 | 2.5 |
| 70 | 4200 | 6.8 | 7.8 | 3.4 |
| 75 | 4500 | 7.3 | 8.8 | 3.8 |
| 80 | 4800 | 7.8 | 9.9 | 4.3 |
| 90 | 5400 | 8.8 | 12.4 | 5.4 |
| 100 | 6000 | 9.8 | 15.0 | 6.5 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 5 | 300 | 0.3 | 0.04 | 0.02 |
| 7 | 420 | 0.5 | 0.05 | 0.02 |
| 10 | 600 | 0.7 | 0.1 | 0.04 |
| 15 | 900 | 1.0 | 0.2 | 0.08 |
| 20 | 1200 | 1.4 | 0.3 | 0.1 |
| 25 | 1500 | 1.7 | 0.5 | 0.2 |
| 30 | 1800 | 2.1 | 0.7 | 0.3 |
| 35 | 2100 | 2.4 | 0.9 | 0.4 |
| 40 | 2400 | 2.7 | 1.2 | 0.5 |
| 45 | 2700 | 3.1 | 1.4 | 0.6 |
| 50 | 3000 | 3.4 | 1.8 | 0.8 |
| 60 | 3600 | 4.1 | 2.5 | 1.1 |
| 70 | 4200 | 4.8 | 3.3 | 1.4 |
| 75 | 4500 | 5.1 | 3.7 | 1.6 |
| 80 | 4800 | 5.5 | 4.2 | 1.8 |
| 90 | 5400 | 6.2 | 5.2 | 2.3 |
| 100 | 6000 | 6.8 | 6.3 | 2.7 |
| 125 | 7500 | 8.6 | 9.6 | 4.2 |
| 150 | 9000 | 10.3 | 13.4 | 5.8 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 5 | 300 | 0.2 | 0.02 | 0.01 |
| 7 | 420 | 0.3 | 0.02 | 0.01 |
| 10 | 600 | 0.4 | 0.03 | 0.01 |
| 15 | 900 | 0.7 | 0.07 | 0.03 |
| 20 | 1200 | 0.9 | 0.1 | 0.05 |
| 25 | 1500 | 1.1 | 0.2 | 0.07 |
| 30 | 1800 | 1.3 | 0.2 | 0.1 |
| 35 | 2100 | 1.6 | 0.3 | 0.1 |
| 40 | 2400 | 1.8 | 0.4 | 0.2 |
| 45 | 2700 | 2.0 | 0.5 | 0.2 |
| 50 | 3000 | 2.2 | 0.6 | 0.3 |
| 60 | 3600 | 2.7 | 0.9 | 0.4 |
| 70 | 4200 | 3.1 | 1.1 | 0.5 |
| 75 | 4500 | 3.3 | 1.3 | 0.6 |
| 80 | 4800 | 3.5 | 1.4 | 0.6 |
| 90 | 5400 | 4.0 | 1.8 | 0.8 |
| 100 | 6000 | 4.4 | 2.2 | 0.9 |
| 125 | 7500 | 5.5 | 3.3 | 1.4 |
| 150 | 9000 | 6.6 | 4.6 | 2.0 |
| 175 | 10500 | 7.7 | 6.2 | 2.7 |
| 200 | 12000 | 8.8 | 7.9 | 3.4 |
| 250 | 15000 | 11.0 | 11.9 | 5.2 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 20 | 1200 | 0.5 | 0.03 | 0.01 |
| 25 | 1500 | 0.6 | 0.04 | 0.02 |
| 30 | 1800 | 0.8 | 0.06 | 0.03 |
| 35 | 2100 | 0.9 | 0.08 | 0.04 |
| 40 | 2400 | 1.0 | 0.1 | 0.05 |
| 45 | 2700 | 1.2 | 0.1 | 0.06 |
| 50 | 3000 | 1.3 | 0.2 | 0.07 |
| 60 | 3600 | 1.5 | 0.2 | 0.1 |
| 70 | 4200 | 1.8 | 0.3 | 0.1 |
| 75 | 4500 | 1.9 | 0.3 | 0.2 |
| 80 | 4800 | 2.1 | 0.4 | 0.2 |
| 90 | 5400 | 2.3 | 0.5 | 0.2 |
| 100 | 6000 | 2.6 | 0.6 | 0.3 |
| 125 | 7500 | 3.2 | 0.9 | 0.4 |
| 150 | 9000 | 3.8 | 1.2 | 0.5 |
| 175 | 10500 | 4.5 | 1.6 | 0.7 |
| 200 | 12000 | 5.1 | 2.1 | 0.9 |
| 250 | 15000 | 6.4 | 3.2 | 1.4 |
| 300 | 18000 | 7.7 | 4.4 | 1.9 |
| 350 | 21000 | 9.0 | 5.9 | 2.6 |
| 400 | 24000 | 10.2 | 7.5 | 3.3 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 30 | 1800 | 0.5 | 0.02 | 0.01 |
| 35 | 2100 | 0.6 | 0.03 | 0.01 |
| 40 | 2400 | 0.7 | 0.03 | 0.01 |
| 45 | 2700 | 0.7 | 0.04 | 0.02 |
| 50 | 3000 | 0.8 | 0.05 | 0.02 |
| 60 | 3600 | 1.0 | 0.07 | 0.03 |
| 70 | 4200 | 1.1 | 0.1 | 0.04 |
| 75 | 4500 | 1.2 | 0.1 | 0.05 |
| 80 | 4800 | 1.3 | 0.1 | 0.06 |
| 90 | 5400 | 1.5 | 0.2 | 0.07 |
| 100 | 6000 | 1.6 | 0.2 | 0.08 |
| 125 | 7500 | 2.0 | 0.3 | 0.1 |
| 150 | 9000 | 2.4 | 0.4 | 0.2 |
| 175 | 10500 | 2.8 | 0.5 | 0.2 |
| 200 | 12000 | 3.3 | 0.7 | 0.3 |
| 250 | 15000 | 4.1 | 1.1 | 0.5 |
| 300 | 18000 | 4.9 | 1.5 | 0.6 |
| 350 | 21000 | 5.7 | 2.0 | 0.9 |
| 400 | 24000 | 6.5 | 2.5 | 1.1 |
| 450 | 27000 | 7.3 | 3.1 | 1.3 |
| 500 | 30000 | 8.1 | 3.7 | 1.6 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 50 | 3000 | 0.6 | 0.02 | 0.01 |
| 60 | 3600 | 0.7 | 0.03 | 0.01 |
| 70 | 4200 | 0.8 | 0.04 | 0.02 |
| 75 | 4500 | 0.8 | 0.05 | 0.02 |
| 80 | 4800 | 0.9 | 0.05 | 0.02 |
| 90 | 5400 | 1.0 | 0.06 | 0.03 |
| 100 | 6000 | 1.1 | 0.08 | 0.04 |
| 125 | 7500 | 1.4 | 0.1 | 0.05 |
| 150 | 9000 | 1.7 | 0.2 | 0.07 |
| 175 | 10500 | 2.0 | 0.2 | 0.1 |
| 200 | 12000 | 2.3 | 0.3 | 0.1 |
| 250 | 15000 | 2.8 | 0.4 | 0.2 |
| 300 | 18000 | 3.4 | 0.6 | 0.3 |
| 350 | 21000 | 3.9 | 0.8 | 0.3 |
| 400 | 24000 | 4.5 | 1.0 | 0.4 |
| 450 | 27000 | 5.1 | 1.3 | 0.6 |
| 500 | 30000 | 5.6 | 1.5 | 0.7 |
| 750 | 45000 | 8.4 | 3.3 | 1.4 |
| 1000 | 60000 | 11.2 | 5.5 | 2.4 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 100 | 6000 | 0.7 | 0.03 | 0.01 |
| 125 | 7500 | 0.8 | 0.04 | 0.02 |
| 150 | 9000 | 1.0 | 0.04 | 0.02 |
| 175 | 10500 | 1.1 | 0.06 | 0.02 |
| 200 | 12000 | 1.3 | 0.07 | 0.03 |
| 250 | 15000 | 1.6 | 0.1 | 0.05 |
| 300 | 18000 | 1.9 | 0.2 | 0.07 |
| 350 | 21000 | 2.3 | 0.2 | 0.09 |
| 400 | 24000 | 2.6 | 0.3 | 0.1 |
| 450 | 27000 | 2.9 | 0.3 | 0.1 |
| 500 | 30000 | 3.2 | 0.4 | 0.2 |
| 750 | 45000 | 4.9 | 0.9 | 0.4 |
| 1000 | 60000 | 6.5 | 1.5 | 0.6 |
| 1250 | 75000 | 8.1 | 2.2 | 1.0 |
| 1500 | 90000 | 9.7 | 3.1 | 1.3 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 200 | 12000 | 0.8 | 0.03 | 0.01 |
| 250 | 15000 | 1.0 | 0.04 | 0.02 |
| 300 | 18000 | 1.2 | 0.05 | 0.02 |
| 350 | 21000 | 1.4 | 0.07 | 0.03 |
| 400 | 24000 | 1.6 | 0.09 | 0.04 |
| 450 | 27000 | 1.9 | 0.1 | 0.05 |
| 500 | 30000 | 2.1 | 0.1 | 0.06 |
| 750 | 45000 | 3.1 | 0.3 | 0.1 |
| 1000 | 60000 | 4.1 | 0.5 | 0.2 |
| 1250 | 75000 | 5.1 | 0.7 | 0.3 |
| 1500 | 90000 | 6.2 | 1.0 | 0.4 |
| 2000 | 120000 | 8.2 | 1.7 | 0.7 |
| 2500 | 150000 | 10.3 | 2.6 | 1.1 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 350 | 21000 | 1 | 0.03 | 0.01 |
| 400 | 24000 | 1.2 | 0.04 | 0.02 |
| 450 | 27000 | 1.3 | 0.05 | 0.02 |
| 500 | 30000 | 1.5 | 0.06 | 0.03 |
| 750 | 45000 | 2.2 | 0.1 | 0.05 |
| 1000 | 60000 | 2.9 | 0.2 | 0.09 |
| 1250 | 75000 | 3.6 | 0.3 | 0.1 |
| 1500 | 90000 | 4.3 | 0.4 | 0.2 |
| 2000 | 120000 | 5.8 | 0.7 | 0.3 |
| 2500 | 150000 | 7.2 | 1.1 | 0.5 |
| 3000 | 180000 | 8.7 | 1.6 | 0.7 |
| 3500 | 210000 | 10.1 | 2.1 | 0.9 |
| 4000 | 240000 | 11.1 | 2.7 | 1.2 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 500 | 30000 | 1.2 | 0.03 | 0.01 |
| 750 | 45000 | 1.8 | 0.07 | 0.03 |
| 1000 | 60000 | 2.4 | 0.1 | 0.05 |
| 1250 | 75000 | 3.0 | 0.2 | 0.08 |
| 1500 | 90000 | 3.6 | 0.3 | 0.1 |
| 2000 | 120000 | 4.7 | 0.5 | 0.2 |
| 2500 | 150000 | 5.9 | 0.7 | 0.3 |
| 3000 | 180000 | 7.1 | 1.0 | 0.4 |
| 3500 | 210000 | 8.3 | 1.3 | 0.6 |
| 4000 | 240000 | 9.5 | 1.7 | 0.7 |
| 4500 | 270000 | 10.7 | 2.1 | 0.9 |
| 5000 | 300000 | 11.9 | 2.5 | 1.1 |
| 5500 | 330000 | 13.1 | 3.0 | 1.3 |
| 6000 | 360000 | 14.2 | 3.6 | 1.5 |
| 6500 | 390000 | 15.4 | 4.1 | 1.8 |
| 7000 | 420000 | 16.6 | 4.7 | 2.0 |
| 7500 | 450000 | 17.8 | 5.4 | 2.3 |
| Volume Flow (gal/min) | Volume Flow (gal/hr) | Velocity (ft/sec) | Friction Head (ft/100 ft) | Friction Loss (psi/100 ft) |
|---|---|---|---|---|
| 500 | 30000 | 0.9 | 0.02 | 0.01 |
| 750 | 45000 | 1.4 | 0.04 | 0.02 |
| 1000 | 60000 | 1.8 | 0.07 | 0.03 |
| 1250 | 75000 | 2.3 | 0.1 | 0.04 |
| 1500 | 90000 | 2.7 | 0.1 | 0.06 |
| 2000 | 120000 | 3.6 | 0.2 | 0.1 |
| 2500 | 150000 | 4.5 | 0.4 | 0.2 |
| 3000 | 180000 | 5.5 | 0.5 | 0.2 |
| 3500 | 210000 | 6.4 | 0.7 | 0.3 |
| 4000 | 240000 | 7.3 | 0.9 | 0.4 |
| 4500 | 270000 | 8.2 | 1.1 | 0.5 |
| 5000 | 300000 | 9.1 | 1.3 | 0.6 |
| 5500 | 330000 | 10.0 | 1.6 | 0.7 |
| 6000 | 360000 | 10.9 | 1.9 | 0.8 |
| 6500 | 390000 | 11.8 | 2.2 | 0.9 |
| 7000 | 420000 | 12.7 | 2.5 | 1.1 |
| 7500 | 450000 | 13.6 | 2.8 | 1.2 |
| 8000 | 480000 | 14.5 | 3.2 | 1.4 |
| 8500 | 510000 | 14.4 | 3.5 | 1.5 |
| 9000 | 540000 | 16.5 | 3.9 | 1.7 |
| 9500 | 570000 | 17.3 | 4.3 | 1.9 |
| 10000 | 600000 | 18.2 | 4.8 | 2.1 |
Pressure loss values can be calculated with the Hazen-Williams Equation or the Darcy-Weisbach Formula.
Related Topics
• Fluid Flow and Pressure Loss in Pipes and Tubes
Fluid flow and pressure loss in pipe lines. Water and sewer systems. Steel pipes, pvc pipes, copper tubes and more.
Related Documents
ASTM D1785 and ASTM F441 - PVC and CPVC Pipes Schedule 40 & 80
Standard dimensions and weight of PVC - Polyvinyl Chloride - and CPVC - Chlorinated Polyvinyl Chloride.
ASTM D2241 - Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series) - Dimensions
Dimensions of PVC pipe SDR series.
EN 1452 - Unplasticized Poly Vinyl Chloride (PVC-U) - Dimensions
Dimensions of PVC-U pipe according EN 1452.
Hazen-Williams Water Flow Formula: Head Loss, Data, Charts & Calculator
Friction head loss (ftH2O per 100 ft pipe) in water pipes can be estimated with the empirical Hazen-Williams equation.
Hot Water Systems - Equivalent Length vs. Fittings Resistance
Equivalent length of fittings like bends, returns, tees and valves in hot water heating systems - equivalent length in feet and meter.
ISO 11922 - Thermoplastics Pipes for the Conveyance of Fluids - Dimensions
Dimensions of plastic pipes according ISO 11922 - metric and imperial units.
ISO 161 - Thermoplastics Pipes - Dimensions
Dimensions of thermoplastic pipes according ISO 161.
Lined Pipes - Pressure Loss vs. Water Flow
Pressure drop diagrams for PTFE, PP, PFA and PVDF lined pipes.
Plastic Pipes - Friction Head Loss vs. Water Flow
Friction head loss (ft/100 ft) vs. water flow in plastic pipes like PVC, PP, PE or PEH.
Plastic Pipes - Maximum Operating Temperatures
Piping materials like ABS, PE, PVC, CPVC, PB, PP and SR and pressure and operating temperature limits.
PVC - Polyvinyl Chloride Pipes - Supports
Distance between PVC pipe supports.
PVC Pipes - Equivalent Length and Pressure Loss in Fittings
Minor loss in PVC and CPVC fittings expressed as equivalent length of straight pipe.
PVC Pipes - Pressure Ratings vs. Size
Maximum operating and required burst pressure of PVC - Polyvinyl Chloride - pipe fittings.
PVC Pipes - Temperature Expansion Loops
Calculate temperature expansion and contraction in PVC piping systems.
PVC Pipes Schedule 40 - Friction Loss vs. Water Flow Diagrams
Friction loss (psi/100 ft) and velocity for water flow in plastic PVC pipe schedule 40.
PVC Pipes Schedule 80 - Friction Loss vs. Water Flow
Water flow in thermoplastic PVC and CPVC pipes Schedule 80 - friction loss (ft/100 ft, psi/100 ft) and flow velocities at dimensions ranging 1/2 to 16 inches.
PVC, CPVC, Carbon Steel, Stainless Steel and Fiberglass Pipes - Thermal Expansion Diagrams
Thermal expansion of PVC, CPVC, Carbon and Stainless Steel and Fiberglass pipes.