Electrical Motors - Frame Dimensions
Dimensions of electrical motor frames according NEMA 1984 are indicated below:
- 1 in (inch) = 25.4 mm
| NEMA Frame Designation | Frame Dimensions (inches) | ||||||
|---|---|---|---|---|---|---|---|
| D | E | 2F | BA | N-W | V | U | |
| 42 | 2 5/8 | 1 3/4 | 1 11/16 | 2 1/16 | 1 1/8 | 3/8 | |
| 42C | 2 5/8 | 1 3/4 | 1 11/16 | 2 1/16 | 1 1/8 | 3/8 | |
| 48 | 3 | 2 1/8 | 2 3/4 | 2 1/2 | 1 1/2 | 1/2 | |
| 48C | 3 | 2 1/8 | 2 3/4 | 2 1/2 | 1 1/2 | 1/2 | |
| 48H | 3 | 2 1/8 | 4 3/4 | 2 1/2 | 1 1/2 | 1/2 | |
| 56 | 3 1/2 | 2 7/16 | 3 | 2 3/4 | 1 7/8 | 5/8 | |
| 56C | 3 1/2 | 2 7/16 | 2 3/4 | 1 7/8 | 5/8 | ||
| 56H | 3 1/2 | 2 7/16 | 5 | 2 3/4 | 1 7/8 | 5/8 | |
| 56HZ | 3 1/2 | 2 7/16 | 5 | 2 3/4 | 2 1/4 | 2 | 7/8 |
| 56J | 3 1/2 | 2 7/16 | 2 3/4 | 2 7/16 | 5/8 | ||
| 66 | 4 1/8 | 2 15/16 | 5 | 3 1/8 | 2 1/4 | 3/4 | |
| 140T | 3 1/2 | 2 3/4 | 4 | 2 3/4 | 2 1/4 | 7/8 | |
| 142AT | 3 1/2 | 2 3/4 | 3 1/4 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 143AT | 3 1/2 | 2 3/4 | 4 | 2 1/4 | 1 3/4 | 1 1/2 | 7/8 |
| 143JM | 3 1/2 | 2 3/4 | 4 | 2 1/4 | 7/8 | ||
| 143JP | 3 1/2 | 2 3/4 | 4 | 2 1/4 | 7/8 | ||
| 143T | 3 1/2 | 2 3/4 | 4 | 2 1/4 | 2 1/4 | 2 | 7/8 |
| 143TC | 3 1/2 | 2 3/4 | 4 | 2 3/4 | 2 1/4 | 7/8 | |
| 143TR | 3 1/2 | 2 3/4 | 4 | 2 1/4 | 2 5/8 | 1 3/4 | 7/8 |
| 144AT | 3 1/2 | 2 3/4 | 4 1/2 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 145AT | 3 1/2 | 2 3/4 | 5 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 145JM | 3 1/2 | 2 3/4 | 5 | 2 1/4 | 7/8 | ||
| 145JP | 3 1/2 | 2 3/4 | 5 | 2 1/4 | 7/8 | ||
| 145T | 3 1/2 | 2 3/4 | 5 | 2 1/4 | 2 1/4 | 2 | 7/8 |
| 145TC | 3 1/2 | 2 3/4 | 5 | 2 3/4 | 2 1/4 | 7/8 | |
| 145TR | 3 1/2 | 2 3/4 | 5 | 2 1/4 | 2 5/8 | 1 3/4 | 7/8 |
| 146AT | 3 1/2 | 2 3/4 | 5 1/2 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 146ATC | 3 1/2 | 2 3/4 | 5 1/2 | 2 3/4 | 2 1/4 | 7/8 | |
| 147AT | 3 1/2 | 2 3/4 | 6 1/4 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 148AT | 3 1/2 | 2 3/4 | 7 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 149AT | 3 1/2 | 2 3/4 | 8 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 1410AT | 3 1/2 | 2 3/4 | 9 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 1411AT | 3 1/2 | 2 3/4 | 10 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 1412AT | 3 1/2 | 2 3/4 | 11 | 2 3/4 | 1 3/4 | 1 1/2 | 7/8 |
| 1412ATC | 3 1/2 | 2 3/4 | 11 | 2 3/4 | 2 1/4 | 7/8 | |
| 162AT | 4 | 3 1/8 | 4 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 163AT | 4 | 3 1/8 | 4 1/2 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 164AT | 4 | 3 1/8 | 2 1/2 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 165AT | 4 | 3 1/8 | 5 1/22 1/2 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 166AT | 4 | 3 1/8 | 6 1/4 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 167AT | 4 | 3 1/8 | 7 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 168AT | 4 | 3 1/8 | 8 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 169AT | 4 | 3 1/8 | 9 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 1610AT | 4 | 3 1/8 | 10 | 2 1/2 | 1 3/4 | 1 1/2 | 7/8 |
| 182 | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 1/4 | 2 | 7/8 |
| L182ACY | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 1/4 | 2 | 7/8 |
| 182AT | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| L182AT | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 | 1 1/8 | |
| 182JM | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 7/8 | ||
| 182JP | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 3/4 | 7/8 | |
| 182T | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 3/4 | 2 1/2 | 1 1/8 |
| 182TC | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 3/4 | 1 1/8 | |
| 182TR | 4 1/2 | 3 3/4 | 4 1/2 | 2 3/4 | 2 1/4 | 2 1/4 | 1 1/8 |
| 183AT | 4 1/2 | 3 3/4 | 5 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 184 | 4 1/2 | 3 3/4 | 5 1/2 | 2 3/4 | 2 1/4 | 2 | 7/8 |
| 184AT | 4 1/2 | 3 3/4 | 5 1/2 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 184JM | 4 1/2 | 3 3/4 | 5 1/2 | 2 3/4 | 7/8 | ||
| 184JP | 4 1/2 | 3 3/4 | 5 1/2 | 2 3/4 | 7/8 | ||
| 184TC | 4 1/2 | 3 3/4 | 5 1/2 | 2 3/4 | 2 3/4 | 1 1/8 | |
| 184T | 4 1/2 | 3 3/4 | 5 1/2 | 2 3/4 | 2 3/4 | 2 1/2 | 1 1/8 |
| 184TR | 4 1/2 | 3 3/4 | 5 1/2 | 2 3/4 | 3 3/8 | 2 1/4 | 1 1/8 |
| 185AT | 4 1/2 | 3 3/4 | 6 1/4 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 186ACY | 4 1/2 | 3 3/4 | 7 | 2 3/4 | 2 1/4 | 2 | 7/8 |
| 186AT | 4 1/2 | 3 3/4 | 7 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| L186AT | 4 1/2 | 3 3/4 | 7 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 186ATC | 4 1/2 | 3 3/4 | 7 | 2 3/4 | 2 1/4 | 1 1/8 | |
| 187AT | 4 1/2 | 3 3/4 | 8 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 188AT | 4 1/2 | 3 3/4 | 9 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 189AT | 4 1/2 | 3 3/4 | 10 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 189ATC | 4 1/2 | 3 3/4 | 10 | 2 3/4 | 2 1/4 | 1 1/8 | |
| 1810AT | 4 1/2 | 3 3/4 | 11 | 2 3/4 | 2 1/4 | 2 | 1 1/8 |
| 203 | 5 | 4 | 5 1/2 | 3 1/8 | 2 1/4 | 2 | 3/4 |
| 204 | 5 | 4 | 6 1/4 | 3 1/8 | 2 1/4 | 2 | 3/4 |
| 213 | 5 1/4 | 4 1/4 | 5 1/2 | 3 1/2 | 3 | 2 3/4 | 1 1/8 |
| 213AT | 5 1/4 | 4 1/4 | 5 1/2 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 213JM | 5 1/4 | 4 1/4 | 5 1/2 | 3 1/2 | 7/8 | ||
| 213JP | 5 1/4 | 4 1/4 | 5 1/2 | 3 1/2 | 1 1/4 | ||
| 213T | 5 1/4 | 4 1/4 | 5 1/2 | 3 1/2 | 3 3/8 | 3 1/8 | 1 3/8 |
| 213TC | 5 1/4 | 4 1/4 | 5 1/2 | 3 1/2 | 3 3/8 | 1 3/8 | |
| 213TR | 5 1/4 | 4 1/4 | 5 1/2 | 3 1/2 | 4 1/8 | 2 5/8 | 1 3/8 |
| 214AT | 5 1/4 | 4 1/4 | 6 1/4 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 215 | 5 1/4 | 4 1/4 | 7 | 3 1/2 | 3 | 2 3/4 | 1 1/8 |
| 215AT | 5 1/4 | 4 1/4 | 7 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 215JM | 5 1/4 | 4 1/4 | 7 | 3 1/2 | 7/8 | ||
| 215JP | 5 1/4 | 4 1/4 | 7 | 3 1/2 | 1 1/4 | ||
| 215T | 5 1/4 | 4 1/4 | 7 | 3 1/2 | 3 3/8 | 3 1/8 | 1 3/8 |
| 215TC | 5 1/4 | 4 1/4 | 7 | 3 1/2 | 3 3/8 | 1 3/8 | |
| 215TR | 5 1/4 | 4 1/4 | 7 | 3 1/2 | 4 1/8 | 2 5/8 | 1 3/8 |
| 216AT | 5 1/4 | 4 1/4 | 8 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 217AT | 5 1/4 | 4 1/4 | 9 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 218AT | 5 1/4 | 4 1/4 | 10 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 219AT | 5 1/4 | 4 1/4 | 11 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 219ATC | 5 1/4 | 4 1/4 | 11 | 3 1/2 | 2 3/4 | 1 3/8 | |
| 2110AT | 5 1/4 | 4 1/4 | 12 1/2 | 3 1/2 | 2 3/4 | 2 1/2 | 1 3/8 |
| 2110ATC | 5 1/4 | 4 1/4 | 12 1/2 | 3 1/2 | 2 3/4 | 1 3/8 | |
| 224 | 5 1/2 | 4 1/2 | 6 3/4 | 3 1/2 | 3 | 2 3/4 | 1 |
| 225 | 5 1/2 | 4 1/2 | 7 1/2 | 3 1/2 | 3 | 2 3/4 | 1 |
| 253AT | 6 1/4 | 5 | 7 | 4 1/4 | 3 1/4 | 3 | 1 5/8 |
| 254 | 6 1/4 | 5 | 8 1/4 | 4 1/4 | 3 3/8 | 3 1/8 | 1 1/8 |
| 254AT | 6 1/4 | 5 | 8 1/4 | 4 1/4 | 3 1/4 | 3 | 1 5/8 |
| 254T | 6 1/4 | 5 | 8 1/4 | 4 1/4 | 4 | 3 3/4 | 1 5/8 |
| 254TC | 6 1/4 | 5 | 8 1/4 | 4 1/4 | 4 | 1 5/8 | |
| 254TR | 6 1/4 | 5 | 8 1/4 | 4 1/4 | 4 1/2 | 2 7/8 | 1 5/8 |
| 254U | 6 1/4 | 5 | 8 1/4 | 4 1/4 | 3 3/4 | 3 1/2 | 1 5/8 |
| 255AT | 6 1/4 | 5 | 9 | 4 1/4 | 3 1/4 | 3 | 1 5/8 |
| 256AT | 6 1/4 | 5 | 10 | 4 1/4 | 3 1/4 | 3 | 1 5/8 |
| 256T | 6 1/4 | 5 | 10 | 4 1/4 | 4 | 3 3/4 | 1 5/8 |
| 256TC | 6 1/4 | 5 | 10 | 4 1/4 | 4 | 1 5/8 | |
| 256TR | 6 1/4 | 5 | 10 | 4 1/4 | 4 1/2 | 2 7/8 | 1 5/8 |
| 256U | 6 1/4 | 5 | 10 | 4 1/4 | 3 3/4 | 3 1/2 | 1 3/8 |
| 257AT | 6 1/4 | 5 | 11 | 4 1/4 | 3 1/4 | 3 | 1 5/8 |
| 258AT | 6 1/4 | 5 | 12 1/2 | 4 1/4 | 3 1/4 | 3 | 1 5/8 |
| 259AT | 6 1/4 | 5 | 14 | 4 1/4 | 3 1/4 | 3 | 1 5/8 |
| 283AT | 7 | 5 1/2 | 8 | 4 3/4 | 3 1/4 | 3 1/2 | 1 7/8 |
| 284 | 7 | 5 1/2 | 9 1/2 | 4 3/4 | 3 3/4 | 3 1/2 | 1 1/4 |
| 284AT | 7 | 5 1/2 | 9 1/2 | 4 3/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 284T | 7 | 5 1/2 | 9 1/2 | 4 3/4 | 4 5/8 | 4 3/8 | 1 7/8 |
| 284TC | 7 | 5 1/2 | 9 1/2 | 4 3/4 | 4 5/8 | 1 7/8 | |
| 284TR | 7 | 5 1/2 | 9 1/2 | 4 3/4 | 4 3/4 | 3 1/8 | 1 7/8 |
| 284TC | 7 | 5 1/2 | 9 1/2 | 4 3/4 | 3 1/4 | 3 | 1 5/8 |
| 284U | 7 | 5 1/2 | 9 1/2 | 4 3/4 | 4 7/8 | 4 5/8 | 1 5/8 |
| 285AT | 7 | 5 1/2 | 10 | 4 3/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 286AT | 7 | 5 1/2 | 11 | 4 3/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 286T | 7 | 5 1/2 | 11 | 4 3/4 | 4 5/8 | 4 3/8 | 1 7/8 |
| 286TC | 7 | 5 1/2 | 11 | 4 3/4 | 4 5/8 | 1 7/8 | |
| 286TR | 7 | 5 1/2 | 11 | 4 3/4 | 4 3/4 | 3 1/8 | 1 7/8 |
| 286TS | 7 | 5 1/2 | 11 | 4 3/4 | 3 1/4 | 3 | 1 7/8 |
| 286U | 7 | 5 1/2 | 11 | 4 3/4 | 4 7/8 | 4 5/8 | 1 7/8 |
| 287AT | 7 | 5 1/2 | 12 1/2 | 4 3/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 288AT | 7 | 5 1/2 | 14 | 4 3/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 289AT | 7 | 5 1/2 | 16 | 4 3/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 323AT | 8 | 6 1/4 | 9 | 4 3/4 | 4 1/4 | 4 | 2 1/8 |
| 324 | 8 | 6 1/4 | 10 1/2 | 5 1/4 | 4 7/8 | 4 5/8 | 1 5/8 |
| 324AT | 8 | 6 1/4 | 10 1/2 | 5 1/4 | 4 1/4 | 4 | 2 1/8 |
| 324TR | 8 | 6 1/4 | 10 1/2 | 5 1/4 | 5 1/4 | 3 1/2 | 2 1/8 |
| 324TS | 8 | 6 1/4 | 10 1/2 | 5 1/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 324U | 8 | 6 1/4 | 10 1/2 | 5 1/4 | 5 5/8 | 5 3/8 | 1 7/8 |
| 325AT | 8 | 6 1/4 | 11 | 5 1/4 | 4 1/4 | 4 | 2 1/8 |
| 326 | 8 | 6 1/4 | 12 | 5 1/4 | 4 7/8 | 4 5/8 | 1 5/8 |
| 326AT | 8 | 6 1/4 | 12 | 5 1/4 | 4 1/4 | 4 | 2 1/8 |
| 326T | 8 | 6 1/4 | 12 | 5 1/4 | 5 1/4 | 5 | 2 1/8 |
| 326TR | 8 | 6 1/4 | 12 | 5 1/4 | 5 1/4 | 3 1/2 | 2 1/8 |
| 326TS | 8 | 6 1/4 | 12 | 5 1/4 | 3 3/4 | 3 1/2 | 1 7/8 |
| 326U | 8 | 6 1/4 | 12 | 5 1/4 | 5 5/8 | 5 3/8 | 1 7/8 |
| 327AT | 8 | 6 1/4 | 14 | 5 1/4 | 4 1/4 | 4 | 2 1/8 |
| 328AT | 8 | 6 1/4 | 16 | 5 1/4 | 4 1/4 | 4 | 2 1/8 |
| 329AT | 8 | 6 1/4 | 18 | 5 1/4 | 4 1/4 | 4 | 2 1/8 |
| 363AT | 9 | 7 | 10 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
| 364 | 9 | 7 | 11 1/4 | 5 7/8 | 5 5/8 | 5 3/8 | 1 7/8 |
| 364AT | 9 | 7 | 11 1/4 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
| 364S | 9 | 7 | 11 1/4 | 5 7/8 | 3 1/4 | 3 | 1 5/8 |
| 364T | 9 | 7 | 11 1/4 | 5 7/8 | 5 7/8 | 5 7/8 | 2 3/8 |
| 364TR | 9 | 7 | 11 1/4 | 5 7/8 | 5 3/4 | 3 3/4 | 2 3/8 |
| 364TS | 9 | 7 | 11 1/4 | 5 7/8 | 3 3/4 | 3 1/2 | 1 7/8 |
| 364U | 9 | 7 | 11 1/4 | 5 7/8 | 6 3/8 | 6 1/8 | 2 1/8 |
| 365 | 9 | 7 | 12 1/4 | 5 7/8 | 5 5/8 | 5 3/8 | 1 7/8 |
| 365AT | 9 | 7 | 12 1/4 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
| 365T | 9 | 7 | 12 1/4 | 5 7/8 | 5 7/8 | 4 7/8 | 2 3/8 |
| 324T | 8 | 6 1/4 | 10 1/2 | 5 1/4 | 5 1/4 | 5 | 2 1/8 |
| 365TR | 9 | 7 | 12 1/4 | 5 7/8 | 5 3/4 | 3 3/4 | 2 3/8 |
| 365TS | 9 | 7 | 12 1/4 | 5 7/8 | 3 3/4 | 3 1/2 | 1 7/8 |
| 365U | 9 | 7 | 12 1/4 | 5 7/8 | 6 3/8 | 6 1/8 | 2 1/8 |
| 366AT | 9 | 7 | 14 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
| 364AT | 9 | 7 | 11 1/4 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
| 367AT | 9 | 7 | 16 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
| 368AT | 9 | 7 | 18 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
| 369AT | 9 | 7 | 20 | 5 7/8 | 4 3/4 | 4 1/2 | 2 3/8 |
- 1 inch = 25.4 mm
Related Topics
• Electrical
Electrical engineering with units, amps and electrical wiring. Wire gauges, electrical formulas, motors and more.
Related Documents
Electric Motors - Efficiency
Calculate electric motor efficiency.
Electric Motors - IEC and NEMA Standard Torques
IEC and NEMA torque classifications of electrical motors.
Electrical Induction Motors - Synchronous Speed
Operating speed of an induction motor depends on the input power frequency and the number of magnetic poles in the motor.
Electrical Motor Calculator: Power, Efficiency & Torque Calculations
Calculate amps, hp and kVA for electrical motors.
Electrical Motors - Full Load Amps
Full load amps for single and 3-phase 460 volts, 230 volts and 115 volts electric motors.
Electrical Motors - Locked Rotor Design Code Letters
NEMA locked rotor indicating code letters for electrical motors.
Electrical Motors - NEMA Frame Assignments
NEMA frame assignments.
Electrical Motors - Shaft Power vs. Voltage and Current
Calculate electric motors shaft power.
Electrical Motors Efficiency Ratings
NEMA - electrical motor efficiency ratings.
NEMA - National Electrical Manufacturers Association
National Electrical Manufacturers Association.
NEMA A, B, C and D Electrical Motor Design
NEMA has established the four different designs A, B, C and D for electrical induction motors.
NEMA Enclosure Standards for Electric Motors
NEMA enclosure standard for electrical motors.
NEMA Insulation Classes
Electrical insulation systems rated by standard NEMA classifications to maximize allowable operating temperatures.
Nema Starters
Nema sized contactors or starters.
Three-Phase Electrical Motors - Power Factor vs. Inductive Load
Inductive loads and power factors with electrical three-phase motors.