Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

EN 1452 - Unplasticized Poly Vinyl Chloride (PVC-U) - Dimensions

Dimensions of PVC-U pipe according EN 1452.

Dimensions of PVC-U pipes according EN 1452 Plastics piping systems for water supply. Unplasticized poly (vinyl chloride) (PVC-U). Fitness for purpose of the system:

For full table with Table Z - rotate the screen!3

EN 1452 - Unplasticized Poly Vinyl Chloride (PVC-U) - Dimensions
Nominal Outside Diameter
(mm)
Min. Wall Thickness (mm)
S 20
SDR 41
S 16.7
SDR 34.4
S 16
SDR 33
S 12.5
SDR 26
S 10
SDR 21
S 8
SDR 17
S 6.3
SDR 13.6
S 5
SDR 11
Nominal Pressure PN (design coefficient 2.5)
PN 6 PN 6 PN 8 PN 10 PN 12.5 PN 16 PN 20
12 1.5
16 1.5
20 1.5 1.9
25 1.5 1.9 2.3
32 1.5 1.6 1.9 2.4 2.9
40 1.5 1.6 1.9 2.4 3.0 3.7
50 1.6 2.0 2.4 3.0 3.7 4.6
63 2.0 2.5 3.0 3.8 4.7 5.8
75 2.3 2.9 3.6 4.5 5.6 6.8
90 2.8 3.5 4.3 5.4 6.7 8.2
Nominal Pressure PN (design coefficient 2.0)
PN 6.3 PN 7.5 PN 8 PN 10 PN 12.5 PN 16 PN 20 PN 25
63 2.0 2.0 2.4 3.0 3.8
75 2.0 2.2 2.9 3.6 4.5
90 2.0 2.7 3.5 4.3 5.4
Nominal Pressure PN (design coefficient 2.0)
PN 6 PN 7.5 Pn 8 PN 10 PN 12.5 PN 16 PN 20 PN 25
110 2.7 3.2 3.4 4.2 5.3 6.6 8.1 10.0
125 3.1 3.7 3.9 4.8 6.0 7.4 9.2 11.4
140 3.5 4.1 4.3 5.4 6.7 8.3 10.3 12.7
160 4.0 4.7 4.9 6.2 7.7 9.5 11.8 14.6
180 4.4 5.3 5.5 6.9 8.6 10.7 13.3 16.4
200 4.9 5.9 6.2 7.7 9.6 11.9 14.7 18.2
225 5.5 6.6 6.9 8.6 10.8 13.4 16.6
250 6.2 7.3 7.7 9.6 11.9 14.8 18.4
280 6.9 8.2 8.6 10.7 13.4 16.6 20.6
315 7.7 9.2 9.7 12.1 15.0 18.7 23.2
355 8.7 10.4 10.9 13.6 16.9 21.1 26.1
400 9.8 11.7 12.3 45.3 19.1 23.7 29.4
450 11.0 13.2 13.8 17.2 21.5 26.7 33.1
500 12.3 14.6 15.3 19.1 23.9 29.7 36.8
560 13.7 16.4 17.2 21.4 26.7
630 15.4 18.4 19.3 24.1 30.0
710 17.4 20.7 21.8 27.2
800 19.6 23.3 24.5 30.6
900 22.0 26.3 27.6
1000 24.5 29.2 30.6

Unit Converter


















































6.29.10



3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!