Engineering ToolBox - Resources, Tools and Basic Information for Engineering and Design of Technical Applications!

Sizing Circular Ducts

A rough guide to maximum air volume capacity of circular ducts in comfort, industrial and high speed ventilation systems.

Maximum air velocity in the ducts should be kept below certain limits to avoid unacceptable noise generation.

ductwork velocity method

The values from the table below can be used for rough sizing of ducts in comfort, industrial and high speed ventilation systems.

For full table with Industrial and High Speed Systems - rotate the screen!

Sizing Circular Ducts

Diameter
(mm)
Area
(m2)
Maximum Air Volume Flow (m3/h)
Comfort systemsIndustrial systemsHigh speed systems
Main ducts Secondary ducts Connecting ducts Main ducts Secondary ducts Connecting ducts Main ducts Secondary ducts Connecting ducts
Speed (m/s)
5.5 4 2 10 6.5 4 14 9 6.5
63 0.003 62 45 22 112 73 45 157 101 73
80 0.005 99 72 36 181 118 72 253 163 118
100 0.008 155 113 57 283 184 113 396 254 184
125 0.012 243 177 88 442 287 177 618 397 287
160 0.020 398 289 145 723 470 289 1013 651 470
200 0.031 622 452 226 1130 735 452 1583 1017 735
250 0.049 971 707 353 1766 1148 707 2473 1590 1148
315 0.078 1542 1122 561 2804 1823 1122 3926 2524 1823
400 0.126 2487 1809 904 4522 2939 1809 6330 4069 2939
500 0.196 3886 2826 1413 7065 4592 2826 9891 6359 4592
630 0.312 6169 4487 2243 11216 7291 4487 15703 10095 7291
800 0.502 9948 7235 3617 18086 11756 7235 25321 16278 11756
1000 0.785 15543 11304 5652 28260 18369 11304 39564 25434 18369
1250 1.227 24286 17663 8831 44156 28702 17663 61819 39741 28702
3D Engineering ToolBox - draw and model technical applications! 2D Engineering ToolBox - create and share online diagram drawing templates! Engineering ToolBox Apps - mobile online and offline engineering applications!

Unit Converter


















































6.27.14

.