Electrical Motors - Single Phase 230 V Circuit Wiring
All wiring and electrical connections should comply with the National Electrical Code (NEC) and local codes and practices.
Recommended copper wire gage and transformer size for single phase 230 Volts electrical motors:
| Motor Power (hp) | Transformer Apparent Power (kVA) | Wire Gauge (AWG) | ||||
|---|---|---|---|---|---|---|
| Distance from Motor to Transformer (feet) | ||||||
| 100 | 150 | 200 | 300 | 500 | ||
| 1.5 | 3 | 10 | 8 | 8 | 6 | 4 |
| 2 | 3 | 10 | 8 | 8 | 8 | 4 |
| 3 | 5 | 8 | 8 | 8 | 4 | 2 |
| 5 | 7.5 | 6 | 4 | 4 | 2 | 0 |
| 7.5 | 10 | 6 | 4 | 3 | 1 | 0 |
With undersized wire between motor and power source the starting and load carrying capabilities of the motor will be limited.
Apparent Power is the power supplied to the electric circuit - typical from a power supplier to the grid - to cover the real and reactive power consumption in the loads.