Electrical Motor Power and Maximum Cable Length
Maximum cable lengths for electrical motors
Three phase 230 V electrical motors and maximum cable length with 3% calculated voltage drop.
Electric Motor Power | Maximum Cable Length (m, ft) | |||
---|---|---|---|---|
(kW) | (hk) | 30 (98) | 50 (164) | 100 (328) |
Cable Size (mm2) | ||||
0.5 | 0.68 | 1.5 | 1.5 | 1.5 |
1 | 1.36 | 1.5 | 1.5 | 1.5 |
1.5 | 2.04 | 1.5 | 1.5 | 1.5 |
2 | 2.76 | 1.5 | 2.5 | 4 |
2.5 | 3.4 | 1.5 | 2.5 | 4 |
3 | 4.08 | 2.5 | 2.5 | 6 |
3.5 | 4.78 | 2.5 | 4 | 6 |
4 | 5.44 | 2.5 | 4 | 6 |
4.5 | 6.12 | 4 | 4 | 10 |
5 | 6.80 | 4 | 4 | 10 |
6 | 8.16 | 6 | 6 | 10 |
7 | 9.52 | 10 | 10 | 16 |
8 | 10.9 | 10 | 10 | 16 |
9 | 12.2 | 10 | 10 | 16 |
10 | 13.6 | 16 | 16 | 16 |
12 | 16.3 | 16 | 16 | 16 |
14 | 19.0 | 16 | 16 | 25 |
16 | 21.8 | 16 | 16 | 25 |
18 | 24.5 | 25 | 25 | 35 |
20 | 27.2 | 25 | 25 | 35 |
22 | 29.9 | 25 | 25 | 35 |
24 | 32.6 | 35 | 35 | 35 |
26 | 35.4 | 35 | 35 | 35 |
28 | 38.1 | 35 | 35 | 50 |
30 | 40.8 | 35 | 35 | 50 |
35 | 47.6 | 50 | 50 | 50 |
40 | 54.4 | 70 | 70 | 70 |
45 | 61.2 | 70 | 70 | 70 |
50 | 68 | 70 | 70 | 70 |
55 | 74.8 | 70 | 70 | 70 |
60 | 81.6 | 95 | 95 | 95 |
65 | 88.4 | 120 | 120 | 120 |
70 | 95.2 | 120 | 120 | 120 |
75 | 102 | 150 | 120 | 150 |
80 | 109 | 150 | 150 | 150 |
85 | 116 | 185 | 150 | 185 |
90 | 122 | 185 | 185 | 185 |
95 | 129 | 185 | 185 | 185 |
100 | 136 | 240 | 240 | 240 |