Three-Phase Electrical Motors

Full load amps - wire and conduit size

Typical full load current, minimum wire size and conduit size 230V and 460V motors are indicated below:

Horsepower Full Load (Amps) Minimum Wire Size (AWG - Rubber) Conduit Size (inches)
230V 460V 230V 460V 230V 460V
1 3.3 1.7 14 14 1/2 1/2
1.5 4.7 2.4 14 14 1/2 1/2
2 6 3 14 14 1/2 1/2
3 9 4.5 14 14 1/2 1/2
5 15 7.5 12 14 1/2 1/2
7.5 22 11 8 14 3/4 1/2
10 27 14 8 12 3/4 1/2
15 38 19 6 10 1-1/4 3/4
20 52 26 4 8 1-1/4 3/4
25 64 32 3 6 1-1/4 1-1/4
30 77 39 1 6 1-1/2 1-1/4
40 101 51 00 4 2 1-1/4
50 125 63 000 3 2 1-1/4
60 149 75 200M 1 2-1/2 1-1/2
75 180 90 0000 0 2-1/2 2
100 245 123 500M 000 3 2
125 310 155 750M 0000 3-1/2 2-1/2
150 360 180 1000M 300M 4 2-1/2