Electric Cable Installations - Current Ratings

Current ratings and cable sizes for fixed installations within buildings

The table below indicates current ratings for fixed cable installations within buildings. The table is based on PVC-wiring and PVC-insulated cables - single wire, fine wires and multi stranded wires.

Installation MethodA1A2B1B2
InstallationSingle core cables, in insulating tubes, in thermally insulated wallsMulti core sheathed cables, in insulating tubes, in thermally insulated wallsSingle core cables, in insulating tubes, on wallsMulti core cables, or multi core sheathed cables, in insulating tubes, on walls

Number of Cores

23232323
Cross-Section
(mm2)
Current Ratings
(ampere)
1.5 15.5 13.5 15.5 13.0 17.5 15.5 16.5 15.0
2.5 19.5 18.0 18.5 17.5 24 21 23 20
4 26 24 25 23 32 28 30 27
6 34 31 32 29 41 36 38 34
10 46 42 43 39 57 50 52 46
16 61 56 57 52 76 68 69 62
25 80 73 75 68 101 89 90 80
35 99 89 92 83 125 110 111 99
50 119 108 110 99 151 134 133 118
70 151 136 139 125 192 171 168 149
95 182 164 167 150 232 207 201 179
120 210 188 192 172 269 239 232 206
150 240 216 219 196
185 273 245 248 223
240 320 286 291 261
300 367 328 334 298
  • operating temperature max. 70 oC
  • ambient temperature max. 70 oC
  • A1 - Single core cables in a conduit in a thermally insulated wall
  • A2 - Multi core cable or multi-core sheathed cable in a conduit in a thermally insulated wall
  • B1 - Single core cables in conduit or wall
  • B2 - Multi core cable or multi-core sheathed cable in a conduit in a wall

Related Topics

  • Electrical - Electrical units, amps and electrical wiring, wire gauge and AWG, electrical formulas and motors

Related Documents

Matched Content

Tag Search

Search the Engineering ToolBox

- "Search is the most efficient way to navigate the Engineering ToolBox!"

Engineering ToolBox - SketchUp Extension - Online 3D modeling!

3D Engineering ToolBox Extension to SketchUp - add parametric components to your SketchUp model

Add standard and customized parametric components - like flange beams, lumbers, piping, stairs and more - to your SketchUp model with the Engineering ToolBox - SketchUp Extension/Plugin - enabled for use with the amazing, fun and free SketchUp Make and SketchUp Pro . Add the Engineering ToolBox extension to your SketchUp from the Sketchup Extension Warehouse!

Translate the Engineering ToolBox!
About the Engineering ToolBox!

close