NEMA and IEC Enclosure Classifications
NEMA enclosure classifications are developed by NEMA and used in the U.S./American market.
Ingress Protection - IP - ratings are developed by the European Committee for Electro Technical Standardization (CENELEC) (described IEC/EN 60529), and specifies the environmental protection and enclosure provided.
The table below can be used to convert from NEMA Enclosure Types to IEC Enclosure Types:
NEMA Enclosure Types | IEC Enclosure Classification Designation | ||
---|---|---|---|
1 | General Purpose - Indoor | IP10 | Protected against solid objects up to 50mm, e.g. accidental touch by hands. |
2 | Drip-Proof - Indoor | IP11 | Protected against solid objects up to 50mm, e.g. accidental touch by hands. Protection against vertically falling drops of water e.g. condensation. |
3 | Dust-tight, Rain-tight, Sleet-tight - Outdoor | IP54 | Protected against dust limited ingress (no harmful deposit). Protection against water sprayed from all directions, limited ingress permitted. |
3R | Rain-tight, Sleet Resistant- Outdoor | IP14 | Protected against solid objects up to 50mm, e.g. accidental touch by hands. Protection against water sprayed from all directions, limited ingress permitted. |
3S | Dust-tight, Rain-tight, Sleet-tight- Outdoor | IP54 | Protected against dust limited ingress (no harmful deposit). Protection against water sprayed from all directions, limited ingress permitted. |
4 | Water-tight, Dust-tight, Sleet Resistant-Indoor & Outdoor | IP56 | Protected against dust limited ingress (no harmful deposit). |
4X | Water-tight, Dust-tight, Corrosion-Resistant- Indoor & Outdoor | IP56 | Protected against dust limited ingress (no harmful deposit). |
5 | Dust-tight, Drip-Proof--Indoor | IP52 | Protected against dust limited ingress (no harmful deposit). Protection against direct sprays of water up to 15o from the vertical. |
6 | Occasionally Submersible, Watertight, Sleet Resistant- Indoor & Outdoor | IP67 | Totally protected against dust. Protected against the effect of immersion between 15cm and 1m. |
6P | Water-tight, Sleet Resistant- Prolonged Submersion- Indoor & Outdoor | IP67 | Totally protected against dust. Protected against the effect of immersion between 15cm and 1m. |
12 | Dust-tight and Drip-tight- Indoor | IP52 | Protected against dust limited ingress (no harmful deposit). Protection against direct sprays of water up to 15o from the vertical. |
12K | Dust-tight and Drip-tight, with Knockouts- Indoor | IP52 | Protected against dust limited ingress (no harmful deposit). Protection against direct sprays of water up to 15o from the vertical. |
13 | Oil-tight and Dust-tight- Indoor | IP54 | Protected against dust limited ingress (no harmful deposit). Protection against water sprayed from all directions, limited ingress permitted. |
Note! NEMA standards meets or exceeds IEC standards. The conversion does not work in the opposite direction.
Related Topics
• Electrical
Electrical engineering with units, amps and electrical wiring. Wire gauges, electrical formulas, motors and more.
Related Documents
Electrical Enclosure Types by NEMA
Description of NEMA electrical enclosures types.
IEC Electric Motor Duty Cycles
The eight - S1 - S8 - IEC duty cycles of operating electrical motors.
IP - Ingress Protection Ratings
IP - Ingress Protection rating is used to specify the environmental protection - or electrical enclosure - of electrical equipment.