The studs sizes for cast iron flanges class 125 and 250 are indicated in the tables below. The sizes are for standard facing and standard pressure ratings flange to flange.
| NPS (in) |
No. of Studs |
Diameter of Stud (in) |
Length of Stud (in) |
| 1/2 | 4 | 1/2 | 2-1/2 |
| 3/4 | 4 | 1/2 | 2-1/2 |
| 1 | 4 | 1/2 | 2-3/4 |
| 1-1/4 | 4 | 1/2 | 2-3/4 |
| 1-1/2 | 4 | 1/2 | 3 |
| 2 | 4 | 5/8 | 3-1/2 |
| 2-1/2 | 4 | 5/8 | 3-3/4 |
| 3 | 4 | 5/8 | 3-3/4 |
| 3-1/2 | 8 | 5/8 | 3-3/4 |
| 4 | 8 | 5/8 | 3-3/4 |
| 5 | 8 | 3/4 | 4 |
| 6 | 8 | 3/4 | 4-1/4 |
| 8 | 8 | 3/4 | 4-1/2 |
| 10 | 12 | 7/8 | 4-3/4 |
| 12 | 12 | 7/8 | 5 |
| 14 | 12 | 1 | 5-1/2 |
| 16 | 16 | 1 | 5-1/2 |
| NPS (in) |
No. of Studs |
Diameter of Stud (in) |
Length of Stud (in) |
| 1/2 | 4 | 1/2 | 2-3/4 |
| 3/4 | 4 | 5/8 | 3-1/4 |
| 1 | 4 | 5/8 | 3-1/4 |
| 1-1/4 | 4 | 5/8 | 3-1/2 |
| 1-1/2 | 4 | 5/8 | 3-3/4 |
| 2 | 8 | 5/8 | 3-3/4 |
| 2-1/2 | 8 | 5/8 | 4-1/4 |
| 3 | 8 | 5/8 | 4-1/2 |
| 3-1/2 | 8 | 5/8 | 4-1/2 |
| 4 | 8 | 5/8 | 4-3/4 |
| 5 | 8 | 5/8 | 5 |
| 6 | 12 | 5/8 | 5 |
| 8 | 12 | 7/8 | 5-3/4 |
| 10 | 16 | 1 | 6-1/2 |
| 12 | 16 | 1-1/8 | 7 |
| 14 | 20 | 1-1/8 | 7-1/4 |
| 16 | 20 | 1-1/4 | 7-3/4 |
| 18 | 24 | 1-1/4 | 8 |