Support Copper Pipework

Maximum spacing between supports for copper tubing

Copper Tube - Maximum spacing between Supports (m)
Outside Diameter (mm) Horizontal Run Vertical Run
15 1.2 1.8
22 1.2 1.8
28 1.5 2.4
35 1.8 3.0
42 1.8 3.0
54 1.8 3.0
6 2.4 3.7
76 2.4 3.7
108 3.0 3.7
Imperial Units
Outside Diameter (in) Maximum spacing between supports (ft)
5/8  5
7/8 6
1 1/8 7
1 5/8 9
2 1/8 10
3 1/8 12
3 5/8 13
4 1/8 14